Category
DAB7n
Introduction Advantages Electrical parameters of DAB7N-40 miniature circuit breakerStandard of conformity: IEC60898, GB1
Basic Info.
Model NO. | DAB7N-40 |
Poles Number | 1p+N |
Type | Circuit Breaker |
Function | Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection, OVP(Overvoltage Protection) |
Certification | ISO9001-2000, CE, CB, CCC |
Width | 18mm |
Transport Package | Carton |
Specification | 6, 10, 16, 20, 25, 32, 40A |
Trademark | CDADA, OEM, ODM |
Origin | Shanghai |
HS Code | 85362000 |
Production Capacity | 10000PCS/Month |
Product Description
Introduction
DAB7N-40 Series miniature circuit breaker adopts double-break point of 1P+N,the two poles are insulated and isolated from each other,under synchronous operation,N-pole always will make first and break later, which guarantees electric arc breaking capacity of protected pole, also ensures safety of controlled circuits and electric equipment. |
Advantages
- Two types of overcurrent protection - thermal and electromagnetic.
- Independent contact position indicator.
- DIN rail latch with a double fixed position.
- Wide range of operating temperatures from -40 to +50° С.
- Wide engagement lever with improved contact area.
- Notches on terminal clamps lower thermal losses and boost the mechanical stability of connection.
Mechanical parameters of DAB7N-40 miniature circuit breakerProtection grade: IP20Electric wire: 1~35mm2Working temperature: -5~+40ºCFlame retardant grade: grade2Altitude: ≤2000Class of pollution: 2Installation environment: Avoid obvious shock and vibrationInstallation grade: grade IIInstallation method: Using 35mm guide rail according to IEC standardTerminal type: Dual-purpose terminal can be connected to the bus bar and conductor.Terminal connection ability: conductor 1-25mm2, bus bar thickness 0.8-2mmGuide rail: DIN35guide rail
Technical Features
MCB DAB7-40 | |||
For protection of general power distribution (IEC/EN 60898-1) | | ||
Poles | 1P | ||
Electrical performance | |||
Functions | short circuit protection,overload protection,isolationg,control | ||
Rated frequency f (Hz) | 50-60Hz | ||
Rated working voltage Ue(V)AC | 230 | ||
Rated current In ( A) | 40 | ||
Rated insulated voltage Ui( V) | 500 | ||
Impulse withstand voltage Uimp(kV) | 4 | ||
Instantaneous tripping type | B/C | ||
Rated short circuit Icn(kA) | DAB7-40 | 6 | |
Release type | Thermal magnetic type | ||
Service life(O~C) | Mechanical | Actual value | 12000 |
Standard value | 4000 | ||
Electrical | Actual value | 6000 | |
Standard value | 4000 | ||
Connection and installation | |||
Protectiom degree | IP20 | ||
Wire mm² | 1~35 | ||
Working temperature | -5 ~+40ºC | ||
Resistance to humidity and heat | Class 2 | ||
Altitude above sea | ≤2000 | ||
Relative humidity | +20ºC , ≤90% ;+40ºC , ≤50% | ||
Pollution degree | 2 | ||
Installation environment | Avoid obvious shock and vibration | ||
Installation class | Class II , Class III | ||
Mounting | DIN35 rail | ||
Combination with accessories | |||
Auxiliary contact | Yes | ||
Alarm contact | Yes | ||
Shunt release | Yes | ||
Undervoltage release | Yes | ||
Auxiliary contact+Alarm contact | Yes | ||
Dimensions(mm) (WxHxL) | a | 18 | |
b | 80.7 | ||
c | 72 |